Перевести страницу

Компетентность. Надежность. Прозрачность.

BS 5467 Copper Conductor Multi Core SWA PVC BASEC 0.6/1kV Cable

BS 5467 Copper Conductor Multi Core SWA PVC BASEC 0.6/1kV Cable
Eland Product Group:  A9S
APPLICATION
Multi-core PVC cable with steel wire armour (SWA). Power and
auxiliary control cables for use in power networks, underground, outdoor and indoor applications and for use in cable ducting.
BS 5467, BS EN/IEC 60502-1, BS EN/IEC 60332-1-2
CONSTRUCTION
Conductor
Class 2 stranded copper conductor according to BS EN 60228 (previously BS 6360)
Insulation
XLPE (Cross-Linked Polyethylene)
Bedding
PVC (Polyvinyl Chloride)
Armour
SWA (Steel Wire Armour)
Sheath
PVC (Polyvinyl Chloride)
The  electrical  and  dimensional  properties  of  this  product  are  measured  by  the Technical and Quality Assurance department at the Eland Cables laboratory. Cable performance in respect of conductor resistance, construction quality (workmanship), dimensional  consistency,  and  other  parameters  are  verified  to  published  standards and  approved  product  drawings.  Conformance  to  RoHS  (Restriction  of  the  use  of Hazardous Substances) is determined and confirmed.
CHARACTERISTICS
Voltage Rating (Uo/U) 600/1000V
Temperature Rating
Fixed: -25°C to +90°C
Minimum Bending Radius
1.5mm2  to 16mm2  - Fixed: 6 x overall diameter 25mm2  and above - Fixed: 8 x overall diameter
Core Identification
2 core:     Brown     Blue
3 core:     Brown     Black     Grey
4 core:     Brown     Blue     Black     Grey
5 core:     Green/Yellow     Brown     Blue     Black     Grey
Alternative Core Identification:
White cores with     Black numbers
Sheath Colour
Black


DIMENSIONS
BS5467 XLPE/PVC/SWA/PVC (Copper)
ELAND PART NO.
NO. OF CORESNOMINAL CROSS SECTIONAL AREA
mm²
NOMINAL THICKNESS OF INSULATION
mm
NOMINAL DIAMETER
mm
NOMINAL WEIGHT
kg/km
BW / CW GLANDWRAPAROUND CLEATS
Under ArmourOverall
A9SWA201521,50,67,312,130220CC5
A9SWA202522,50,78,513,634620CC6
A9SWA2040240,79,414,741020SCC7
A9SWA2060260,710,515,949920CC7
A9SWA2102100,712,31864820CC8
A9SWA2162160,714,320,497820CC9
A9SWA2252250,914,720,4129025CC9
A9SWA2352350,916,823,3150025CC10
A9SWA25025011925,8189025CC11
A9SWA2702701,12229245032CC12
A9SWA2952951,125,133,1330032CC14
A9SWA212021201,227,936,1402040CC16
A9SWA215021501,430,939,3475040CC16
A9SWA301531,50,67,812,633020CC5
A9SWA302532,50,79,214,139020SCC6
A9SWA3040340,71015,346420SCC7
A9SWA3060360,711,216,656820CC7
A9SWA3103100,713,119,586620CC8
A9SWA3163160,715,321,6115225CC9
A9SWA3253250,918,923,6180025CC11
A9SWA3353350,921,325,7223032CC12
A9SWA350350121,728,5249032CC12
A9SWA3703701,125,232,2329032CC14
A9SWA3953951,128,837444040CC16
A9SWA312031201,23240,4547040CC16
A9SWA315031501,435,945,5693050SCC18
A9SWA318531851,64049,8835063SCC20
A9SWA324032401,744,955,11040063S-
A9SWA330033001,849,860,21260063S-
A9SWA34003400255,866,61460075S-
A9SWA401541,50,68,513,336520SCC6
A9SWA402542,50,79,91543820CC6
A9SWA4040440,71116,453220CC7
A9SWA4060460,712,318,776420CC8
A9SWA4104100,714,521,1101325CC9
A9SWA4164160,71723,4136025CC10
A9SWA4254250,92126,1216032CC11
A9SWA4354350,923,628,6269032CC12
A9SWA45045012532313032CC14
A9SWA4704701,129,537,7450040CC16
A9SWA495
4951,133,341,7560050SCC18
A9SWA412041201,237,547,1740050CC20
A9SWA415041501,441,651,4878050-
A9SWA418541851,646,456,61063063S-
A9SWA424042401,752,6631339063-
A9SWA430043001,85868,81629075S-
A9SWA44004400265,478,11980090-
A9SWA501551,50,69,714,341020SCC6
A9SWA502552,50,711,716,147020CC7
A9SWA5040540,71317,871020CC7
A9SWA5060560,714,52087625CC8
A9SWA5105100,717,222,9116525CC10
A9SWA5165160,72026,6174232CC11
A9SWA5255250,924,731,5232332CC14
A9SWA5355350,927,834,8293240CC14
A9SWA550550132,440,4419250SCC16
A9SWA071571,50,610,215,247020SCC6
A9SWA702572,50,712,317,160020CC7
A9SWA7040740,713,619,188120CC8
A9SWA1215121,50,613,719,478020CC8
A9SWA12025122,50,716,322,4100025CC9
A9SWA1915191,50,616,222,2100025CC9
A9SWA1925192,50,719,926,6154025CC11
A9SWA2715271,50,62026,7150032CC11
A9SWA2725272,50,72430,7195032CC14
A9SWA3715371,50,622,329180032CC12
A9SWA3725372,50,726,933,8235040CC14


CONDUCTORS
Class 2 Stranded Conductors for Single Core and Multi-Core Cables
NOMINAL CROSS SECTIONAL AREA
mm²
MINIMUM NO. OF WIRES IN CONDUCTORMAXIMUM RESISTANCE OF CONDUCTOR AT 20ºC
CircularCircular CompactedShapedAnnealed Copper Conductor
CuAlCuAlCuAlPlain Wires
ohms/km
1,57-6---12,1
2,57-6---7,41
47-6---4,61
67-6---3,08
107766--1,83
167766--1,15
257766660,727
357766660,524
50191966660,387
701919121212120,268
951919151515150,193
1203737181518150,153
1503737181518150,124
1853737303030300,0991
2403737343034300,0754
3006161343034300,0601
4006161535353530,047

The above table is in accordance with BS EN 60228 (previously BS 6360)


ELECTRICAL CHARACTERISTICS XLPE/PVC/SWA/PVC
Current Carrying Capacity
NOMINAL CROSS SECTIONAL AREA
mm²
REFERENCE METHOD C (CLIPPED DIRECT)
Amps
REFERENCE METHOD E
(IN FREE AIR OR ON A PERFORATED CABLE TRAY,  HORIZONTAL OR VERTICAL)
Amps
REFERENCE METHOD D (DIRECT IN GROUND OR IN DUCTING IN GROUND,  IN OR AROUND BUILDINGS)
Amps
1 Two Core Cable
Single-Phase AC or DC
1 Three or
1 Four Core Cable
Three-Phase AC
1 Two Core Cable Single-Phase
AC or DC
1 Three or
1 Four Core Cable Three-Phase
AC
1 Two Core Cable Single-Phase
AC or DC
1 Three or
1 Four Core Cable Three-Phase
AC
1,5272329252521
2,5363139333328
4494252444336
6625366565344
10857390787158
1611094115999175
2514612415213111696
35180154188162139115
50219187228197164135
70279238291251203167
95338289354304239197
120392335410353271223
150451386472406306251
185515441539463343281
240607520636546395324
300698599732628446365
400787673847728--
Air ambient temperature: 30ºC Ground ambient temperature: 20ºC
Conductor operating temperature: 90ºC
Notes
1. Where a conductor operates at a temperature exceeding 70ºC it must be ascertained that the equipment connected to the conductor is suitable for the conductor operating temperature (see Regulation 512.1.2 of the 17th Edition of IEE Wiring Regulations).
2. Where cables in this table are connected to equipment or accessories designed to operate at a temperature not exceeding 70ºC , the current ratings given in the equivalent table for 70ºC thermoplastic insulated cables (Table 4D4A) must be used (see also Regulation 523.1 of the 17th Edition of IEE Wiring Regulations).
The above table is in accordance with Table 4E4A of the 17th Edition of IEE Wiring Regulations.